Home, limit, alarm, dock and enable interface requirements

Work record: #59. This is a proposed review checklist and source adapter boundary, not a reviewed/as-built electrical design. ADR-0006, the local safety interface matrix and wiring gaps remain controlling references. No real interface is enabled by this record.

Each future enabled real channel needs an exact named circuit/terminal/firmware/hardware revision, manufacturer data, signed review/evidence record and declared test stage. The adapter must reject missing, changed or incompatible records. A label such as home, a reserved cable core or a software Boolean cannot substitute for those facts.

Interface Required circuit and behavioral facts before enablement Current adapter
Per-axis home Sensor type/placement, GPIO/terminal map, supply and voltage/isolation, active/inactive polarity, startup bias, open/short/power-loss detectability, debounce, permitted axis order/direction/rate/travel/time and reference plausibility/repeatability Unavailable; synthetic channel only
Independent hard limits Distinct locations/channels, wiring/polarity/failure detection, direct independent stopping/interlock path, fault priority and worst-case latency, reset/manual recovery behavior Unavailable; software fixture is not a hard limit
CL57Y alarm Exact delivered driver/manual revision and output characteristics, isolation/level translation, alarm polarity and boot/transient behavior, cable failure semantics, fault persistence and reset procedure Unavailable; encoder/current/following error are not exposed
Driver enable / pulse permissions Exact driver terminals/selector/interface, GPIO reset/default/brownout state, independent isolation and restraint, state-dependent response and electrical/mechanical timing Unavailable; no enable GPIO assigned
Dock and latch Separate physical sensors, polarity and cable-failure behavior, geometry/alignment versus positive engagement, contact bounce, loss/contradiction and local state-owner interpretation Unavailable; no coordinate-only Parked inference
Tension/position Actual fitted sensor/interface, calibrated units/frame/uncertainty/freshness, failure detection and capability prerequisites Unavailable; commanded/estimated values are not protection evidence

The review must distinguish sampled software debounce from independent hard-limit/emergency-isolation paths. Single-channel GPIO readings do not inherently distinguish an inactive switch from a broken cable. RAW_DISCONNECTED is an injected source fixture until an approved circuit can detect that condition. Define startup, loss of sensor power, stuck-on/off, noise, connector removal and contradictory-channel behavior for the actual installation. No generic enable-off command proves braking or line restraint.

Before a secured physical test, record as-built continuity/polarity inspection, exact sensor/driver/cabinet revisions, isolation/signal thresholds and timing, mechanical restraint, permitted axis order, relative travel/time/rate envelope, stop/isolation access and recovery procedure. Record repeatability and fault outcomes on that setup. Loaded and installed acceptance remains governed by the commissioning gates. This source checklist clears none of them.